    Модель SIC-5A-EB SIC-10A-EB
    Refrigerant Capacity kW 10 20
    kcal/hr 8,600 17,200
    Compressor Type Scroll
    Input power (kW) 3.3 6.6
    Refrigerant Filling Volume (kg) 7.5 15
    Control Mode Capillary
    Type R410A
    Evaporator Type Tube style
    Condenser Type Fin style
    Blower power (kW) 0.19x2 0.25x2
    Water Tank Capacity L 55 145
    Water pump (50Hz) Power (kW) 0.37 0.75
    Pump flow (L/min) 60
    Working Pressure (Bar) 2.0
    Total Power kW 4.05 7.85
    Pipe Coupling (inch) Chilled Water Outlet 1
    Chilled Water Inlet 1
    Water Tank Drainage Port 1/2
    Water Tank Overflow Port 1/2
    Protective Devices Compressor Built-in protective switch/Overload Relay
    Pump Overload Relay
    Refrigeration Loop High and Low pressure controller
    Power ЗФ, 400VAC, 50Hz
    Measures Exchange 1kW=860kcal/hr 1RT=3,024kcal/hr 10,000 Btu/hr= 2,520kcal/hr
    Цена
     

    ■ Features

    • Cooling range 7~25°C
    • Stainless steel insulated water tank, with prolonged service life and free of contanmination.
    • Adopt R410 A refrigerant with good refrigeration effect.
    • Refrigerating system adopts multiple precise controls that accurately control the system stability.
    • Compressor and pump overload protection.
    • Fin-style condenser with quick heat conduction and good dissipation effect.
    • Adopt tube and shell evaporator.The copper pipe is directly mounted on water tank that is economical and practical.
    • Adopt renowned brand of original precision temperature- controlled meter with an accuracy of ±0.1°C.

    Рисунок1.jpg


    ■ Application

    SIC-A-EB series are applicable for cooling moulds to reduce products molding cycle time; also they are available in the cooling of equipments in order to maintain a normal temperature. Besides, they are suitable for other industries with the need of cooling.


    ■ Working Principle

    SIC-A-EB air cooled water chiller mainly consists of compressor, condenser, capillary and tube evapo­rator. Adopting single-stage vapor compression refrigerating system, gas-liquid adsorption and release, it achieves the cooling effect.

    When SIC-A-EB air-cooled water chiller starting up, compressor (A) starts working. Refrigerant is compressed into high temperature high pressure gas, and then be cooled when passing through condenser (C) and changed into liquid. Heat is taken away by the cooling air. The liquid high pressure refrigerant passes through the capillary (F), and partial refrigerant is changed into gas under reduced pressure. At this time, the refrigerant is mixed with gas and liquid, which cools down the chilled water into required temperature after passing through the tube evaporator(l) . By heat adsorption , the liquid refrigerant changes to gas and returns the compressor for this circulation.

    Рисунок3.jpg

    ■ Outline Drawings
    Рисунок4.jpg

    Outline Drawings
    Рисунок5.jpg

    Model selection References
    Рисунок6.jpg

    Structure of Air-cooled Models
    Рисунок7.jpg

    ■ Схема корпуса (SIC-5A-EB)

    Рисунок8.jpg


    Список деталей корпуса (SIC-5A-EB)

    Рисунок9.jpg


    ■ Структурная схема системы хладагента (SIC-5A-EB)

    Рисунок10.jpg


    Список деталей системы хладагента (SIC-5A-EB)

    Рисунок11.jpg


    ■ Структурная схема водной системы (SIC-5A-EB)

    Рисунок12.jpg


    Список деталей водной системы (SIC-5A-EB)

    Рисунок13.jpg


    Сборочный чертеж (SIC-10A-EB)

    Рисунок14.jpg


    Список деталей (SIC-10A-EB)

    Рисунок15.jpg


    ■ Чертеж корпуса (SIC-10A-EB)

    Рисунок16.jpg


    Список деталей корпуса (SIC-10A-EB)

    Рисунок17.jpg


    Структурная схема системы хладагента (SIC-10A-EB)

    Рисунок18.jpg


    Список деталей системы хладагента (SIC-10A-EB)

    Рисунок19.jpg


    ■ Структурная схема водной системы (SIC-10A-EB)

    Рисунок20.jpg


    Список деталей водной системы (SIC-10A-EB)

    Рисунок21.jpg


    Похожие товары